# Troubleshooting – LumiScan VGR

This page describes known problems with LumiScan VGR, grouped by category. Start with the [general checks](https://docs.hdvisionsystems.com/en/lumiscan-vgr/1.8.4/troubleshooting.html#general-checks): they explain where to find the information that the diagnostic steps use. Then find your symptom in the categories below and follow the steps of the entry.

## General checks {#general-checks}

- **Admin mode:** Press **Ctrl + Shift + A** to switch admin mode on or off. The **PROFINET** tab (T2) and the **Scene** tab (T1) are only visible in admin mode. The admin controls (A2 to A14) are only active in manual mode. For PLC diagnostics, activate admin mode but do not activate manual mode: while manual mode is active, PLC-controlled processing is paused.
- **Status and return code:** The result of each action is shown as a status message in the status window (S2), for example **SUCCESS**. For PROFINET, it is also shown as a number in `OUT_ReturnCode` in the **PROFINET** tab. OPC UA methods return the code as the string `ReturnCode`. The meaning of each value is listed in [PLC Settings: Status Information](https://docs.hdvisionsystems.com/en/lumiscan-vgr/1.8.4/plc-settings.html#status-information) and in the [FAQ](https://docs.hdvisionsystems.com/en/lumiscan-vgr/1.8.4/faq.html#faq-return-codes).
- **Operation mode:** Most functions require the operation mode `AUTOMATIC` (`1`). For PROFINET, the current mode is shown in `OUT_OperationMode`. For OPC UA, `GetOperationMode` returns it.
- **Log files:** Log files are stored in `<HDVAppData>\LumiScan VGR\logs`, where `HDVAppData` is `C:\Users\<UserName>\AppData\Local\HD Vision Systems GmbH`. The log files rotate: each file has a maximum size of 10 MB, and at most five files are kept. The log window opens with S3. In debug mode (**Ctrl + Shift + D**, or the start option `-d` / `--debug`), the console shows the same detailed output that is written to the log file. If the application crashes, a memory dump is created in `<HDVAppData>\LumiScan VGR`.
- **Camera:** LumiScan VGR requires a LumiScanX camera connected to the IPC via Ethernet. The camera network, the Windows Firewall and the virus protection must be configured as described in the LumiScanX manual: [Network Settings](https://docs.hdvisionsystems.com/en/lumiscan-x/2.0.0/installation.html#sec-network-settings), [Windows Firewall](https://docs.hdvisionsystems.com/en/lumiscan-x/2.0.0/installation.html#sec-windows-firewall) and [Virus Protection](https://docs.hdvisionsystems.com/en/lumiscan-x/2.0.0/installation.html#sec-virus-protection).
- **Licence:** For problems with the LumiScan Key or CodeMeter Runtime, see [Licensing: Troubleshooting](https://docs.hdvisionsystems.com/en/lumiscan-licensing/1.0.4/troubleshooting.html).

## Start-up and camera {#startup-and-camera}

### Problem: The camera is not recognized or no image is captured after start-up {#faq-setup-required}

**Symptoms**

After LumiScan VGR has started, the camera is not recognized and no image can be captured. Trigger Camera (PROFINET) or `CaptureImage` (OPC UA) returns `CAMERA_NOT_INITIALIZED` (`2`).

**Possible causes**

- The application has not been initialized (Setup). Automatic setup at start (`enableAutomaticSetup`) is disabled by default.
- The camera was reset with the Reset Camera function, and Setup has not been executed again.

**Diagnostic procedure**

1. PROFINET: In the **PROFINET** tab (admin mode), check `OUT_IsSetup`. Expected: `1` (system setup has been completed).
2. OPC UA: Check that the client has called `SetupSystem` at least once since the application started. Expected: `SetupSystem` returned `SUCCESS`.
3. In the settings file, check `enableAutomaticSetup` in the `system` section. If it is missing or `false` (default), Setup is not executed automatically at start.
4. Check whether the camera was reset since the last Setup (PROFINET: Reset Camera function with `IN_ResetCameraRequest`; OPC UA: `ResetCamera`).

**Resolution**

- **If the application has not been initialized:** Run Setup before you capture an image:
  - PLC: Run the Setup function with `IN_SetupRequest`. Check: `OUT_IsSetup` is `1`.
  - OPC UA: Call `SetupSystem`. Check: it returns `SUCCESS`.
  - User interface: Activate manual mode (M1), then initialize the application with A6 in admin mode.
  - After Setup, capture an image again. Check: the image is displayed in the **Image** tab (T0), and the status window (S2) shows **SUCCESS**.
- **If the camera was reset:** Run Setup again as described above. After resetting the camera, Setup must be executed again.
- **If Setup should run automatically at start:** Set [`enableAutomaticSetup`](https://docs.hdvisionsystems.com/en/lumiscan-vgr/1.8.4/api/settings/system-settings.html#system-settings-enable-automatic-setup) to `true` in the `system` section.

**If the problem persists**

Send the information listed under [Information for support](https://docs.hdvisionsystems.com/en/lumiscan-vgr/1.8.4/troubleshooting.html#support-information) to support, together with the return code of Trigger Camera or `CaptureImage` and the settings file.

### Problem: Image capture fails with a camera return code {#ts-camera-error-code}

**Symptoms**

No images are acquired from the LumiScanX sensor system. Trigger Camera (PROFINET) or `CaptureImage` (OPC UA) returns one of these codes:

- `CAMERA_NOT_CONNECTED` (`3`): A connection to the camera could not be established.
- `CAMERA_ACQUISITION_ERROR` (`4`): An error occurred while communicating with or acquiring data from the camera.
- `CAMERA_HARDWARE_TRIGGER_AGAIN` (`12`): Auto-exposure was unsuccessful.
- `CAMERA_BAD_EXPOSURETIME_SETTING` (`13`): The requested exposure time cannot be reached.
- OPC UA only: `CAMERA_RESTART_REQUIRED`: The camera driver or firmware requires a restart.

**Possible causes**

- The camera hardware is not reachable, for example because of the cabling or the camera network.
- Image acquisition failed because of an exposure, trigger or transport problem.
- Auto-exposure did not reach a valid exposure.
- The configured exposure range is too short or too long for the current lighting conditions.
- The camera driver or firmware requires a restart.

**Diagnostic procedure**

1. Read the return code in the status window (S2), in `OUT_ReturnCode` (PROFINET) or in `ReturnCode` (OPC UA). Expected: `SUCCESS` (`0`). Note the code: it identifies the cause.
2. Check the cabling of the LumiScanX camera. Expected: the camera is connected to the IPC via Ethernet.
3. Check the camera network as described in [LumiScanX: Network Settings](https://docs.hdvisionsystems.com/en/lumiscan-x/2.0.0/installation.html#sec-network-settings).
4. Open the log window (S3) and check the entries at the time of the capture.
5. For `CAMERA_HARDWARE_TRIGGER_AGAIN` or `CAMERA_BAD_EXPOSURETIME_SETTING`: Check the [auto-exposure settings](https://docs.hdvisionsystems.com/en/lumiscan-vgr/1.8.4/api/settings/autoexposure-settings.html) of the camera in the `cameras` section. In debug mode, the yellow auto-exposure polygon in the **Image** tab shows the region used for the auto-exposure computation (`polygon`).

**Resolution**

- **If the camera is not reachable (`CAMERA_NOT_CONNECTED`):**
  1. Check the cabling and the camera network as described in the LumiScanX manual.
  2. Reset the camera: PROFINET: Reset Camera function (`IN_ResetCameraRequest`, camera ID in `IN_ParamArgString`); OPC UA: `ResetCamera` (an empty string resets all cameras).
  3. Run Setup again. After resetting the camera, Setup must be executed again.
  4. Capture an image. Check: the return code is `SUCCESS` (`0`).
- **If image acquisition failed (`CAMERA_ACQUISITION_ERROR`):** Reset the camera and run Setup again as described above. If the error remains, check the LumiScanX documentation.
- **If auto-exposure was unsuccessful (`CAMERA_HARDWARE_TRIGGER_AGAIN`):** Trigger the camera again (Trigger Camera or `CaptureImage`). Check: the return code is `SUCCESS` (`0`).
- **If the exposure time cannot be reached (`CAMERA_BAD_EXPOSURETIME_SETTING`):** Check the auto-exposure settings, or contact HD Vision Systems.
- **If a restart of the camera is required (`CAMERA_RESTART_REQUIRED`, OPC UA):** Call `ResetCamera`.

**If the problem persists**

Send the information listed under [Information for support](https://docs.hdvisionsystems.com/en/lumiscan-vgr/1.8.4/troubleshooting.html#support-information) to support, together with the return code, the camera serial number and the `cameras` section of the settings file.

### Problem: A timeout message appears or only a black image is captured, although the camera is detected {#faq-black-image-timeout}

**Symptoms**

A timeout message appears. During capture, only a black image is displayed, although the connected sensor is detected and appears in the drop-down menu.

**Possible causes**

- The Windows Firewall is not configured correctly and blocks the devices.
- The virus protection blocks the devices.

**Diagnostic procedure**

1. Check the network configuration of the LumiScanX camera as described in [LumiScanX: Network Settings](https://docs.hdvisionsystems.com/en/lumiscan-x/2.0.0/installation.html#sec-network-settings).
2. Check the Windows Firewall settings as described in [LumiScanX: Windows Firewall](https://docs.hdvisionsystems.com/en/lumiscan-x/2.0.0/installation.html#sec-windows-firewall). Expected: the devices are not blocked by the firewall.
3. Check the virus protection settings as described in [LumiScanX: Virus Protection](https://docs.hdvisionsystems.com/en/lumiscan-x/2.0.0/installation.html#sec-virus-protection).

**Resolution**

- **If the Windows Firewall blocks the devices:** Configure the Windows Firewall as described in the LumiScanX manual. Then capture an image again. Check: the image is not black, and no timeout message appears.
- **If the virus protection blocks the devices:** Configure the virus protection as described in the LumiScanX manual, then capture an image again.

**If the problem persists**

Send the information listed under [Information for support](https://docs.hdvisionsystems.com/en/lumiscan-vgr/1.8.4/troubleshooting.html#support-information) to support, together with the exact timeout message and the camera serial number.

## PLC communication (PROFINET) {#plc-communication-profinet}

### Problem: LumiScan VGR does not respond after GripBestResult {#faq-no-reaction-plc-request}

**Symptoms**

The PLC has sent a GripBestResult request (`IN_GripBestResultRequest`), but the application does not return the expected result. LumiScan VGR seems to hang. The same procedure applies when LumiScan VGR does not respond to another PLC request, for example Trigger Camera, Compute Objects, Get Best Result, Set Parameter, Get Parameter or Setup. Replace `GripBestResult` in the signal names below with the name of that function.

**Possible causes**

- The PROFINET connection is interrupted.
- The application is still executing the function.
- The PLC handshake is incomplete, for example the PLC has not reset `IN_GripBestResultRequest` to `0`, or has set it before `OUT_GripBestResultReady` was `1`.
- The PLC has not set the request, for example because a condition in the PLC program is not met.
- LumiScan VGR is not in the operation mode `AUTOMATIC`.
- The application is in an unexpected internal state.

**Diagnostic procedure**

1. **Verify the PROFINET connection.** Activate admin mode with **Ctrl + Shift + A**. Do not activate manual mode. Open the **PROFINET** tab (T2). Expected: the tab shows the data currently exchanged with the PLC. Ask the PLC programmer whether the PLC still has a connection to LumiScan VGR.

2. **Check the heartbeat signals.** In the **PROFINET** tab, watch `IN_HeartBeat` and `OUT_HeartBeat`. Expected: both blink red and green; `OUT_HeartBeat` follows `IN_HeartBeat`. If they do not blink, the PROFINET connection is lost. The PLC heartbeat is enabled with [`enableHeartbeat`](https://docs.hdvisionsystems.com/en/lumiscan-vgr/1.8.4/api/settings/system-settings.html#system-settings-enable-heartbeat) in the `system` section (default `true`).

3. **Verify the request and response signals.** In the **PROFINET** tab, check the signals and compare them with [Table 5: PLC Data Transmission Process](https://docs.hdvisionsystems.com/en/lumiscan-vgr/1.8.4/plc-settings.html#process-flow):
   - `OUT_OperationMode`: expected `1` (`AUTOMATIC`).
   - `OUT_Error`: expected `0`; `1` means that LumiScan VGR is in an error state.
   - Before the request: `OUT_GripBestResultReady` is `1` and `OUT_GripBestResultRunning` is `0`.
   - After the PLC has set `IN_GripBestResultRequest` to `1` (shown as **True**, green): `OUT_GripBestResultReady` changes to `0` and `OUT_GripBestResultRunning` to `1`. If `IN_GripBestResultRequest` stays **False**, LumiScan VGR has not received the request.
   - The PLC then resets `IN_GripBestResultRequest` to `0`. LumiScan VGR executes the function only after the request is back at `0`.
   - When the function is finished: `OUT_GripBestResultRunning` is `0` and `OUT_GripBestResultReady` is `1`.
   - If the PLC considers the last step as not finished: check that `OUT_SetParameterReady`, `OUT_TriggerCameraReady`, `OUT_ComputeObjectsReady`, `OUT_GetBestResultReady`, `OUT_GripBestResultReady` and `OUT_GetParameterReady` are `1`, and that `OUT_SetParameterRunning`, `OUT_TriggerCameraRunning`, `OUT_ComputeObjectsRunning`, `OUT_GetBestResultRunning`, `OUT_GripBestResultRunning` and `OUT_GetParameterRunning` are `0`.
   - Note the handshake step at which the signals stop changing.

4. **Inspect the application logs.** Open the log window (S3), or open the log file `LumiScanVGR.log` in `<HDVAppData>\LumiScan VGR\logs`. Search for `PLC - Procedure "GripBestResult" called` and `PLC - Procedure "GripBestResult" finished`. Expected: both entries exist for the time of the request. If `called` is missing, the function was not called by the PLC. If `called` exists but `finished` is missing, the function has not finished.

   Possible function names in these entries: `TriggerCamera`, `ComputeObjects`, `GetBestResult`, `GripBestResult`, `SetParameter`, `GetParameter`, `Setup`.

5. **Record the return code.** After `OUT_GripBestResultRunning` has changed to `0`, read `OUT_ReturnCode` in the **PROFINET** tab and the status message in the status window (S2). Expected: `0` (`SUCCESS`) or `10` (`RESULTS_EMPTY`). For `10`, see [Problem: `RESULTS_EMPTY` is returned](https://docs.hdvisionsystems.com/en/lumiscan-vgr/1.8.4/troubleshooting.html#faq-results-empty). For other values, see [Table 6: Return Values](https://docs.hdvisionsystems.com/en/lumiscan-vgr/1.8.4/plc-settings.html#status-information).

**Resolution**

- **If the PROFINET connection is interrupted** (`IN_HeartBeat` and `OUT_HeartBeat` do not blink):
  1. Ask the PLC programmer to check the PROFINET connection on the PLC side.
  2. If `enableHeartbeat` is set to `false` in the `system` section, set it to `true` and start LumiScan VGR again with the changed settings file.
  3. Check: `IN_HeartBeat` and `OUT_HeartBeat` blink red and green again.
  4. Send the request again, starting with step 1 of the handshake.

- **If the application is still executing** (`OUT_GripBestResultRunning` is `1`, the request is back at `0`, and the log contains `called` but not yet `finished`): Wait until `OUT_GripBestResultRunning` is `0`. Then check the return code and read the output variables (handshake steps 14 to 16). Check: the log contains `PLC - Procedure "GripBestResult" finished`.

- **If the PLC handshake is incomplete:** Make sure that the PLC program follows the handshake:
  1. Wait until `OUT_GripBestResultReady` is `1`.

  2. Set `IN_GripBestResultRequest` to `1`.

  3. Wait until `OUT_GripBestResultReady` is `0`, and check that `OUT_GripBestResultRunning` is `1`. If `OUT_GripBestResultRunning` does not become `1`, the trigger is discarded; start again with step 1.

  4. Set `IN_GripBestResultRequest` to `0`.

  5. Wait until `OUT_GripBestResultRunning` is `0`, check the return code and read the output variables.

     Check: `OUT_GripBestResultReady` is `1` again, and `OUT_ReturnCode` is `0` or `10`.

- **If the PLC has not set the request** (`IN_GripBestResultRequest` stays **False** in the **PROFINET** tab, and the log contains no `called` entry): Ask the PLC programmer to check whether the PLC program has an unmet condition for setting the request, whether the PLC is waiting for a signal, and whether a PLC-internal check that is not related to LumiScan VGR blocks the process (for example a robot error or a cylinder error). Check: `IN_GripBestResultRequest` changes to **True** (green) in the **PROFINET** tab.

- **If LumiScan VGR is not in the operation mode `AUTOMATIC`:** See [Problem: The PLC cannot start any functions after manual mode](https://docs.hdvisionsystems.com/en/lumiscan-vgr/1.8.4/troubleshooting.html#faq-manual-mode-plc).

- **If the application is in an unexpected internal state:** If the PLC sets the request to **True**, but the **PROFINET** tab still shows it as **False**, LumiScan VGR has an internal error due to execution concurrency. If `OUT_Error` is `1`, LumiScan VGR is in an error state. In both cases, inform HD Vision Systems and send the information listed below.

**If the problem persists**

Send the information listed under [Information for support](https://docs.hdvisionsystems.com/en/lumiscan-vgr/1.8.4/troubleshooting.html#support-information) to support, together with:

- the software version (**Ctrl + Shift + V**) and the operating system of the IPC,
- the relevant logs: the exported log file `LumiScanVGR.log` that covers the time of the request,
- the date and time of the error,
- the communication status: a screenshot of the **PROFINET** tab in admin mode, the values of `OUT_ReturnCode`, `OUT_OperationMode` and `OUT_Error`, and, if possible, the saved status of the PLC variables,
- the handshake step at which the PLC or LumiScan VGR stops,
- whether the PLC still has a connection to LumiScan VGR, whether the PLC is waiting for signals, and whether the PLC has already set the request signal,
- whether the PLC has internal checks or process status checks that are not related to LumiScan VGR (for example a robot error or a cylinder error).

### Problem: The PLC cannot start any functions after manual mode {#faq-manual-mode-plc}

**Symptoms**

After manual mode has been used, the PLC can no longer start processing functions. `OUT_OperationMode` shows `2` (`MANUAL`) while manual mode is active, or `0` (`IDLE`) after manual mode has been exited.

**Possible causes**

- Manual mode is still active. While manual mode is active, PLC-controlled processing is paused.
- Manual mode has been exited. The system then changes to `IDLE` (`0`), in which only parameter-setting functions are available.

**Diagnostic procedure**

1. In the **PROFINET** tab (admin mode), check `OUT_OperationMode`. Expected: `1` (`AUTOMATIC`).
2. In the user interface, check whether manual mode is active. Manual mode is active when the manual controls (M2) and the workflow steps M3 to M6 are displayed.

**Resolution**

- **If manual mode is still active:** Exit manual mode in the user interface. The PLC cannot switch the system out of manual mode. The system then changes to `IDLE` (`0`); continue with the next step.
- **If the system is in `IDLE`:** Set the operation mode back to `AUTOMATIC` from the PLC with the Set Parameter function:
  1. Set `IN_ParamId` to `0` (`SET_OPERATION_MODE`) and `IN_ParamArgByte` to `1` (`AUTOMATIC`).
  2. Run Set Parameter with `IN_SetParameterRequest`, following the handshake ([Table 5](https://docs.hdvisionsystems.com/en/lumiscan-vgr/1.8.4/plc-settings.html#process-flow)).
  3. Check: `OUT_ReturnCode` is `0`, and `OUT_OperationMode` is `1`.

**If the problem persists**

Send the information listed under [Information for support](https://docs.hdvisionsystems.com/en/lumiscan-vgr/1.8.4/troubleshooting.html#support-information) to support, together with the values of `OUT_OperationMode` and `OUT_ReturnCode` after Set Parameter.

## OPC UA {#opc-ua}

### Problem: OPC UA calls fail with `BadTimeout` or `BadResourceUnavailable` {#faq-opcua-timeout}

**Symptoms**

A method call fails on the client with `BadTimeout` or a transport disconnect, or it is rejected with `BadResourceUnavailable`.

**Possible causes**

- The client method call timeout is too short. Many methods take significantly longer than standard PLC operations; the typical execution time is 3 to 10 seconds. Default SDK timeouts (often 2 to 5 seconds) are too short.
- Another client is currently executing a method, or the client calls methods in parallel. The server processes one method at a time; parallel calls are rejected with `BadResourceUnavailable`.

**Diagnostic procedure**

1. Check the method call timeout configured in the OPC UA client. Expected: at least 15 seconds.
2. Check whether the client calls methods in parallel, and whether a second client is connected (at most 2 clients can be connected at the same time). Expected: only one method is executed at a time.

**Resolution**

- **If the call timeout is too short:** Set the client method call timeout to at least 15 seconds. Check: the method returns a `ReturnCode` instead of `BadTimeout`.
- **If another client is executing a method, or methods are called in parallel:** Do not call methods in parallel. If another client is executing a method, wait and retry. Check: the call is no longer rejected with `BadResourceUnavailable`.

**If the problem persists**

Send the information listed under [Information for support](https://docs.hdvisionsystems.com/en/lumiscan-vgr/1.8.4/troubleshooting.html#support-information) to support, together with the method that fails, the error reported by the client and the configured client timeouts.

### Problem: OPC UA methods return `OPERATION_MODE_INVALID` {#ts-opcua-operation-mode-invalid}

**Symptoms**

OPC UA methods return `OPERATION_MODE_INVALID`. Only `SetOperationMode` and `GetOperationMode` are accepted.

**Possible causes**

- The server is not in the operation mode `AUTOMATIC`, for example because it is in `IDLE` or `MANUAL` (local or user-interface control active).

**Diagnostic procedure**

1. Call `GetOperationMode`. Expected: `Mode` is `1` and `ModeName` is `AUTOMATIC`.

**Resolution**

- **If the server is not in `AUTOMATIC`:** Call `SetOperationMode` with the value `1` (`AUTOMATIC`), then retry the method. Check: `GetOperationMode` returns `1`, and the method no longer returns `OPERATION_MODE_INVALID`.

**If the problem persists**

Send the information listed under [Information for support](https://docs.hdvisionsystems.com/en/lumiscan-vgr/1.8.4/troubleshooting.html#support-information) to support, together with the result of `GetOperationMode` and the `ReturnCode` of `SetOperationMode`.

### Problem: `CameraTemperature` is `-273.1528` {#ts-opcua-camera-temperature}

**Symptoms**

`GetCameraTemperature` returns `-273.1528` in `CameraTemperature`.

**Possible causes**

- The camera does not report a temperature.

**Diagnostic procedure**

1. Check the value of `CameraTemperature`. `-273.1528` means that the value is unavailable; it is not a physical reading.

**Resolution**

- **If the camera does not report a temperature:** Treat the value as "unavailable", not as a measured temperature.

**If the problem persists**

Contact support with the information listed under [Information for support](https://docs.hdvisionsystems.com/en/lumiscan-vgr/1.8.4/troubleshooting.html#support-information).

### Problem: `Shutdown` has no effect {#ts-opcua-shutdown-no-effect}

**Symptoms**

After a call of the OPC UA method `Shutdown`, LumiScan VGR keeps running.

**Possible causes**

- Remote shutdown is not yet implemented. `Shutdown` is a placeholder and has no effect on the running process.

**Diagnostic procedure**

1. Check on the host machine whether the LumiScan VGR process is still running after the `Shutdown` call. Expected: it is still running; `Shutdown` has no effect.

**Resolution**

- **If remote shutdown is required:** Stop the server process on the host machine.

**If the problem persists**

Contact support with the information listed under [Information for support](https://docs.hdvisionsystems.com/en/lumiscan-vgr/1.8.4/troubleshooting.html#support-information).

## Configuration and detection results {#configuration-and-detection}

### Problem: `RESULTS_EMPTY` is returned {#faq-results-empty}

**Symptoms**

Get Best Result or Grip Best Result (PROFINET), or `GetBestResult` or `GripBestResult` (OPC UA), returns `RESULTS_EMPTY` (`10`): no valid grip points are available for the active robot. In manual mode, the status changes to **RESULTS_EMPTY** after **DONE** (M6); no confirmation is displayed and no training data is exported.

**Possible causes**

- The objects have not been computed yet.
- All candidates of the last detection have already been consumed. Each Grip Best Result call returns the next candidate.
- No objects have been detected (object count `0`).
- The 3D information is invalid, for example because of a poor point cloud or an incorrect configuration.

**Diagnostic procedure**

1. Check that Compute Objects (PROFINET) or `ComputeObjects` (OPC UA) was executed after the last image capture. Expected: it returned `SUCCESS`.
2. Check the number of objects:
   - PROFINET: `OUT_NumObjects` is the number of objects in the scene that have not yet been gripped. With Get Parameter, `IN_ParamId` `0` (`GET_NUM_OBJECTS_2D_TOTAL`) returns the total number of objects detected in 2D, and `1` (`GET_NUM_OBJECTS_3D_TOTAL`) the number of 3D-detected objects that have not yet been gripped.
   - OPC UA: `ComputeObjects` returns `NumObjects2D` and `NumObjects3D`; `GetReport` with `ParamId` `0` or `1` returns the totals.
3. Compare the object counts. If no objects have been detected in 2D, see [Problem: No objects are detected (object count is `0`)](https://docs.hdvisionsystems.com/en/lumiscan-vgr/1.8.4/troubleshooting.html#ts-no-objects-detected). If objects have been detected but none is left to grip, all candidates have been consumed.
4. In admin mode, open the **Scene** tab (T1). Enable **Show Cloud** (Sc3) to display the point cloud, and **Show Grip Candidates** (Sc4, with **Show Origin** disabled) to display the grip candidates. Expected: the point cloud covers the objects, and grip candidates are displayed.

**Resolution**

- **If the objects have not been computed, or all candidates have been consumed:** Capture a new image and compute the objects again (PROFINET: Trigger Camera and Compute Objects; OPC UA: `CaptureImage` and `ComputeObjects`). Check: Get Best Result returns `SUCCESS` (`0`).
- **If no objects have been detected:** See [Problem: No objects are detected (object count is `0`)](https://docs.hdvisionsystems.com/en/lumiscan-vgr/1.8.4/troubleshooting.html#ts-no-objects-detected).
- **If the 3D information is invalid:** Check the point cloud in the **Scene** tab, and check the configuration of the active camera, pipeline and robot in the settings file.

**If the problem persists**

Send the information listed under [Information for support](https://docs.hdvisionsystems.com/en/lumiscan-vgr/1.8.4/troubleshooting.html#support-information) to support, together with the object counts and the recorded data of the capture (see [Generated Data and Files](https://docs.hdvisionsystems.com/en/lumiscan-vgr/1.8.4/output-data.html)).

### Problem: No objects are detected (object count is `0`) {#ts-no-objects-detected}

**Symptoms**

After Compute Objects, the object count is `0`: OPC UA `ComputeObjects` returns `NumObjects2D` and `NumObjects3D` as `0`, or PROFINET Get Parameter `GET_NUM_OBJECTS_2D_TOTAL` returns `0` in `OUT_NumObjects`. The **Image** tab (T0) shows no detection results.

**Possible causes**

- The camera placement or the lighting does not allow the objects to be detected.
- The objects are outside the region of interest (ROI), the purple rectangle in the **Image** tab in which the network searches for objects.
- The wrong pipeline is active, or the pipeline configuration does not match the objects.
- The neural network does not yet provide sufficiently robust detection results for the objects.

**Diagnostic procedure**

1. In the **Image** tab (T0), check the captured image. Expected: the objects are visible and lie inside the purple ROI rectangle.
2. Check the active pipeline. OPC UA: read `ActivePipeline`. Expected: the pipeline that is configured for these objects.
3. Check the pipeline configuration in the `pipelines` section of the settings file. Expected: the pipeline contains the objects to be detected.

**Resolution**

- **If the camera placement or the lighting is not suitable:** Correct the camera placement or the lighting, then capture an image and compute the objects again. Check: the object count is greater than `0`.
- **If the objects are outside the ROI:** Place the objects inside the ROI, or correct the ROI of the pipeline in the settings file.
- **If the wrong pipeline is active:** Select the correct pipeline before you compute the objects (PROFINET: Set Parameter with `IN_ParamId` `2` = `SET_PIPELINE_ID`, ID in `IN_ParamArgString`; OPC UA: `SetActivePipeline`).
- **If the detection is not robust enough:** Use [manual mode](https://docs.hdvisionsystems.com/en/lumiscan-vgr/1.8.4/manual-mode.html) to correct the detected objects and labels and to create new training data.

**If the problem persists**

Send the information listed under [Information for support](https://docs.hdvisionsystems.com/en/lumiscan-vgr/1.8.4/troubleshooting.html#support-information) to support, together with the captured image and the `pipelines` and `objects` sections of the settings file.

### Problem: No point cloud matching can be performed {#ts-no-point-cloud-matching}

**Symptoms**

No point cloud matching can be performed: the generated point cloud is not compared with the 3D models of the objects.

**Possible causes**

- The HALCON licence is not installed.
- The HALCON installation is not part of the `PATH` environment variable.

**Diagnostic procedure**

1. Check that a valid HALCON licence is installed on the IPC.
2. In PowerShell, display the `PATH` environment variable. Expected: it contains the absolute path to the HALCON `bin` directory.

**Resolution**

- **If the HALCON licence is not installed:** Install a valid HALCON licence.
- **If the HALCON installation is not in `PATH`:** Add the absolute path to the HALCON `bin` directory to the `PATH` environment variable. Check: in PowerShell, `PATH` contains this directory.

**If the problem persists**

Send the information listed under [Information for support](https://docs.hdvisionsystems.com/en/lumiscan-vgr/1.8.4/troubleshooting.html#support-information) to support, together with the content of the `PATH` environment variable.

### Problem: A function returns `ID_DOES_NOT_EXIST` {#ts-id-does-not-exist}

**Symptoms**

Selecting a camera, pipeline, robot or recipe returns `ID_DOES_NOT_EXIST` (`8`): PROFINET Set Parameter with `SET_CAMERA_ID`, `SET_PIPELINE_ID` or `SET_ROBOT_ID`, or OPC UA `SetActiveCamera`, `SetActivePipeline`, `SetActiveRobot`, `ExecuteSimpleRecipe` or `ExecuteRecipe`.

**Possible causes**

- The camera, pipeline, robot or recipe ID is not configured in the settings file.
- OPC UA: the ID was added or changed in the configuration after the server started. The arrays `PossibleCameras`, `PossiblePipelines` and `PossibleRobots` are filled at server startup.

**Diagnostic procedure**

1. Compare the ID with the `id` entries in the `cameras`, `pipelines` and `robots` sections of the settings file, and with the recipe IDs in the project configuration. Expected: the ID matches exactly.
2. PROFINET: In the **PROFINET** tab, check `IN_ParamId` and `IN_ParamArgString`. Expected: `IN_ParamArgString` contains the ID.
3. OPC UA: Read `PossibleCameras`, `PossiblePipelines` or `PossibleRobots`. Expected: the ID is listed.

**Resolution**

- **If the ID is not configured:** Use an ID that is configured, or add the component to the settings file. Check: the function returns `SUCCESS` (`0`).
- **If the ID was added or changed after the server started:** Restart the server so that it picks up the new configuration. Check: the ID is listed in the `Possible*` arrays.

**If the problem persists**

Send the information listed under [Information for support](https://docs.hdvisionsystems.com/en/lumiscan-vgr/1.8.4/troubleshooting.html#support-information) to support, together with the ID used and the settings file.

### Problem: A function returns `MISSING_TRANSFORM` {#ts-missing-transform}

**Symptoms**

A function returns `MISSING_TRANSFORM` (`9`): the required coordinate transformation is not available.

**Possible causes**

- Hand-eye calibration data is missing for the active robot-camera pair.

**Diagnostic procedure**

1. Check which camera and robot are active (OPC UA: read `ActiveCamera` and `ActiveRobot`; PROFINET: the IDs last set with `SET_CAMERA_ID` and `SET_ROBOT_ID`).
2. In the `robots` section of the settings file, check [`cameraToRobot`](https://docs.hdvisionsystems.com/en/lumiscan-vgr/1.8.4/api/settings/robot-settings.html#robot-settings-camera-to-robot) of the active robot. Expected: it contains an entry for the active camera ID with a valid 4x4 transformation matrix.

**Resolution**

- **If the hand-eye calibration data is missing:** Add the hand-eye transformation for the camera ID to `cameraToRobot` of the robot, or select a robot-camera pair for which hand-eye calibration data exists. Check: the function returns `SUCCESS` (`0`).

**If the problem persists**

Send the information listed under [Information for support](https://docs.hdvisionsystems.com/en/lumiscan-vgr/1.8.4/troubleshooting.html#support-information) to support, together with the `robots` section of the settings file.

## Hand-eye calibration {#hand-eye-troubleshooting}

These problems occur in LumiScan Hand-Eye Calibration. The **Pose Status** of each captured image is shown in the image list on the **Hand-Eye** tab.

### Problem: Pose Status shows "Can not be interpreted" {#ts-hand-eye-cannot-be-interpreted}

**Symptoms**

After capture, **Pose Status** shows the message `Can not be interpreted`.

**Possible causes**

- The position read out by the PLC appears to be wrong because the PLC is not used for **Pose Mode**.
- LumiScan Hand-Eye Calibration is not connected to the PLC.
- The cifX card name is wrong.

**Diagnostic procedure**

1. On the **Setup** tab, check **Pose Mode**. Expected: `SPS` (the PLC is used for Pose Mode).

2. On the **PROFINET** tab, check the message area. Expected: no connection error message. If a message such as `Hilscher card not connected!` is shown, the connection to the PLC has not been established.

   ![PROFINET tab of LumiScan Hand-Eye Calibration with the connection error message highlighted in red](https://docs.hdvisionsystems.com/en/lumiscan-vgr/1.8.4/_images/Problem_tabelle03.png)

3. On the **Setup** tab, check **CifX Card Name** in the **SPS Layout** group. Expected: the name of the Hilscher card, normally `cifx0;0` if you have only one Hilscher card.

   ![Setup tab of LumiScan Hand-Eye Calibration with the CifX Card Name field in the SPS Layout group highlighted in red](https://docs.hdvisionsystems.com/en/lumiscan-vgr/1.8.4/_images/Problem_tabelle04.png)

**Resolution**

- **If the PLC is not used for Pose Mode:** Set **Pose Mode** to `SPS`, then capture again. Check: **Pose Status** no longer shows `Can not be interpreted`.
- **If LumiScan Hand-Eye Calibration is not connected to the PLC:** Establish the connection to the PLC. Check: the **PROFINET** tab shows no connection error message. Then capture again.
- **If the cifX card name is wrong:** Enter the correct card name in **CifX Card Name** (normally `cifx0;0` with one Hilscher card). Check: the **PROFINET** tab shows no connection error message. Then capture again.

**If the problem persists**

Send the information listed under [Information for support](https://docs.hdvisionsystems.com/en/lumiscan-vgr/1.8.4/troubleshooting.html#support-information) to support, together with screenshots of the **Setup** and **PROFINET** tabs.

### Problem: Pose Status shows "Bad pose quality." {#ts-hand-eye-bad-pose-quality}

**Symptoms**

After capture, **Pose Status** shows the message `Bad pose quality.`

**Possible causes**

- The program cannot detect the pattern of the calibration plate well. This can lead to a poor calibration.

**Diagnostic procedure**

1. On the **Hand-Eye** tab, check the **Pose Status** of each image in the image list. Note the images that show `Bad pose quality.`

**Resolution**

- **If the pattern is not detected well:**
  1. Delete the image.
  2. Change the orientation of the calibration plate.
  3. Capture a new image. Check: **Pose Status** of the new image does not show `Bad pose quality.`

**If the problem persists**

Send the information listed under [Information for support](https://docs.hdvisionsystems.com/en/lumiscan-vgr/1.8.4/troubleshooting.html#support-information) to support, together with a screenshot of the **Hand-Eye** tab.

### Problem: No image is added after capture {#ts-hand-eye-no-image-added}

**Symptoms**

After capture, no image is added to the image list.

**Possible causes**

- The calibration pattern is not found.

**Diagnostic procedure**

1. Check whether the image is overexposed or underexposed (too bright or too dark).
2. Check that the camera can see the pattern points on the calibration plate.

**Resolution**

- **If the calibration pattern is not found:**
  1. Correct the exposure if the image is too bright or too dark.
  2. Make sure that the camera can see the pattern points on the plate.
  3. Change the orientation of the calibration plate.
  4. Capture again. Check: the image is added to the image list.

**If the problem persists**

Send the information listed under [Information for support](https://docs.hdvisionsystems.com/en/lumiscan-vgr/1.8.4/troubleshooting.html#support-information) to support, together with a captured image of the calibration plate.

### Problem: The calibration result is very poor {#ts-hand-eye-poor-result}

**Symptoms**

The calibration result is very poor, for example T:Max > 0.02 (the limit depends on the application). The dialog **Success** shows the calibration error as RMS and MAX values for `T` and `R`:

![Success dialog showing the calibration error with RMS and MAX values for T and R](https://docs.hdvisionsystems.com/en/lumiscan-vgr/1.8.4/_images/Problem_tabelle01.png)

**Possible causes**

- Too many or too few calibration images have been captured.
- The calibration plate is too far away from the camera.
- The viewing angles of the calibration images differ too little.

**Diagnostic procedure**

1. Count the captured calibration images. Expected: between 6 and 15 images.
2. Check whether the captured images match the recommended orientation of the calibration plate.
3. Check that the viewing angles of the images differ clearly, and that the plate is not too far away from the camera.

**Resolution**

- **If too many or too few images have been captured:** Capture between 6 and 15 images.
- **If the plate is too far away from the camera:** Move the calibration plate closer to the camera and capture the images again.
- **If the viewing angles differ too little:** Capture the images at clearly different viewing angles, in the recommended orientations of the calibration plate.

After the calibration, check the calibration error in the dialog **Success**. Expected: it is within the limit of your application.

**If the problem persists**

Send the information listed under [Information for support](https://docs.hdvisionsystems.com/en/lumiscan-vgr/1.8.4/troubleshooting.html#support-information) to support, together with a screenshot of the dialog **Success** and the number of images captured.

## Information for support {#support-information}

Send this information to support:

- **Software version:** Press **Ctrl + Shift + V** to display the build version, or start LumiScan VGR with `-v` / `--version`. Via OPC UA, read `Version`, `GitRevision` and `BuildTime` under `LumiScanVGR/Version`.
- **Operating system:** The Windows version of the IPC (LumiScan VGR requires Windows 11), and the installed NVIDIA GPU, CUDA and cuDNN versions.
- **Logs:** The log files from `<HDVAppData>\LumiScan VGR\logs` (`LumiScanVGR.log`), and the memory dump from `<HDVAppData>\LumiScan VGR` if the application crashed. `HDVAppData` is `C:\Users\<UserName>\AppData\Local\HD Vision Systems GmbH`.
- **Diagnostic information:** S4 collects diagnostic information about the application; the collected data can be encrypted and sent to HD Vision Systems. To include camera data, enable **Camera png** and **Camera ply** under **Export** in **Admin Settings** (A1) first.
- **Time of the error:** The date and time at which the error occurred.
- **Communication status:**
  - PROFINET: a screenshot of the **PROFINET** tab in admin mode, the values of `OUT_ReturnCode`, `OUT_OperationMode` and `OUT_Error`, and, if possible, the saved status of the PLC variables.
  - OPC UA: the method called, its `ReturnCode` or the error reported by the client (for example `BadTimeout`), and the result of `GetOperationMode`.
- **Configuration:** The JSON settings file that was loaded at start.
- **Messages and serial numbers:** The exact message from the status window or the log, a screenshot, the camera serial number and, for licence problems, the serial number of the LumiScan Key.

Contact HD Vision Systems customer success at [customer.success@hdvisionsystems.com](mailto:customer.success@hdvisionsystems.com) or +49 6221 6721905. For licences, contact [licenses@hdvisionsystems.com](mailto:licenses@hdvisionsystems.com).